03Commercial

Whole-building air leakage testing for commercial projects

A commercial air leakage test measures how much air escapes through a building's outer shell. Large fans pressurize or depressurize the whole building, and we record the airflow needed to hold a set pressure. The result is compared with the limit your local code sets. We also find leaks, so a failed building can be fixed and retested. Coming soon: we are adding code compliance testing, and getting the certifications now. Tell us about your project and we will tell you where we are.

Illustration

01What it includes

A test of the shell, a leak search and a report

  1. 01

    Test planning

    We read the plans, find the building envelope area and decide how many fans the building needs. We have a blower door frame that holds three fans, for larger buildings.

  2. 02

    Building preparation

    Intentional openings such as dampers and vents are closed or sealed, and the mechanical systems are set for the test. We send a checklist to the contractor ahead of time.

  3. 03

    The test

    Fans are set in an exterior door frame. We take readings at several pressures, and record weather and temperature on the day.

  4. 04

    Leak finding

    While the building is pressurized, we use infrared imaging and smoke to find leaks at the roof edge, wall joints, penetrations, dock doors and glazing frames.

  5. 05

    Retest

    After the contractor seals the leaks, we test again. Many teams book a mid-construction test and a final test.

  6. 06

    Written report

    The report records the building, the date, the method, the envelope area, the result and the limit, in a clear format.

02The standard

Limits set by Larimer County and Fort Collins

The limit is a leakage rate: cubic feet per minute of air (cfm) for each square foot of building envelope, measured at 75 pascals. A lower number means a tighter building.

RequirementValueNotes and source
Larimer County, commercial buildings0.35 cfm per sq ft of envelope at 75 pascalsLarimer County requires air leakage testing for new residences and commercial buildings. Its commercial limit is in section C402.6.2 of its amended code. The county's handout says the tester must be an approved third party.Source: Larimer County, air leakage and blower door testing, checked Nov 16, 2026
Fort Collins, new commercial buildings, additions and major renovations0.25 cfm per sq ft of envelope at 75 pascalsApplies to buildings under the International Building Code, not the residential code. The city's protocol names ASTM E779 or ASTM E1827 as the test method.Source: City of Fort Collins, commercial building air leakage test protocol, checked Nov 16, 2026
Fort Collins, small commercial buildings0.25 cfm50 per sq ft of surface areaFor buildings under 5,000 sq ft and no more than two stories, the city has a simpler protocol at 50 pascals.Source: City of Fort Collins, alternative small commercial air barrier testing protocol, checked Nov 16, 2026

Other jurisdictions set their own limits. Confirm the code edition and limit with your building department.

03How it works

Getting a commercial building to pass

  1. Know the limit

    We confirm which code and limit apply to the project and who needs the report.

  2. Test mid-construction if you can

    Once the barrier is in place and still exposed, a test finds problems that are cheap to fix.

  3. Final test

    When the building is closed in and the mechanical systems are set, we run the test that counts and issue the report.

  4. If it fails

    We give a leak list.

What you receive

  • The measured leakage rate and the stated limit
  • The test method and equipment used
  • Envelope area and how it was found
  • Leak locations from infrared and smoke
  • A written report for your file

04Who and when

Who needs a commercial air leakage test

Who it is for

  • General contractors on new commercial buildings, additions and major renovations.
  • Architects who detailed the air barrier and want proof it works.
  • Owners who want a tight, efficient building and lower bills.
  • Mechanical engineers sizing equipment for a tight shell.

When you need it

  • After an envelope retrofit.
  • When a building is hard to heat or cool.
A hand holds an infrared camera, its screen showing a thermal image of a wall

In the field

An infrared camera shows where outside air is getting in.

An infrared camera, its screen showing a thermal image of a wall.

05Duct leakage testing

Duct leakage tests for commercial air systems

Ducts that leak lose conditioned air to ceilings, shafts and roofs. A duct leakage test finds out how much. It is often tied to a mechanical spec or a code.

  1. 01

    What is tested

    Supply, return and exhaust duct sections, on rooftop units, split systems and air handlers. A fan pressurizes a sealed section and we measure the airflow needed to hold a set pressure.

  2. 02

    Sections or whole systems

    On large jobs, a spec may test sections as they go in, before ceilings close. On smaller jobs, the whole system may be tested at the end.

  3. 03

    The standard and limit

    The limit comes from the project spec or the code your jurisdiction adopted. Commercial duct jobs often reference a duct construction standard.

  4. 04

    If a system fails

    We point to the likely leak, the contractor seals it, and we retest and report the new result.

06Questions

Questions we hear

Something else? Call 970-657-4197.

What is air barrier testing?

It is a test of how well a building's outer shell blocks air. We pressurize the whole building with fans and measure how much air leaks through. The result is shown as cubic feet per minute for each square foot of envelope.

What are the commercial air leakage requirements?

They depend on your jurisdiction. Larimer County sets 0.35 cfm per square foot at 75 pascals for commercial buildings. Fort Collins sets 0.25 for new buildings, additions and major renovations. Check your own building department.

Which test standard applies?

The Fort Collins protocol names ASTM E779 or ASTM E1827 for commercial buildings. ASTM E3158 and ANSI/RESNET/ICC 380 also appear in local residential rules.

How much does an air barrier test cost?

It depends on the building's size and how many fans it needs. Our frame holds three fans for larger buildings.

What happens if we fail?

We give you a list of where the air is getting in. Your contractor seals those spots, and we retest. The retest result goes into the report.